New construction of Acrel-6000 electrical fire monitoring system in substation of 10KV Shenyang Shenyang Cadre Life Base

This paper introduces the functions and significance of the Acrel-6000 electrical fire monitoring system through the introduction of the Harbin Ford 4S shop electrical fire monitoring system project.
Yang Junjun

Ankerui Electric Co., Ltd. Shanghai Jiading

1 Introduction

The Shenyang Office of the Air Force Officer Housing Development Center of the Shenyang Military Region of the People's Liberation Army (Shenyang Shenyang Cadre Life Base) is a residential complex located at the intersection of Weinan Middle Road and Changqing Street in Shenyang City. The residential area is divided into two parts: the above-ground house and the underground garage. In addition to closed management, the residential and residential community patterns are basically the same. The B1 floor of the low-pressure garage is provided with three substations of self-dimension, pump house and heat exchange station for all power supply of the entire community.

2. System requirements analysis

Detection of leakage current, over current, over temperature and other signals, sound and light signal alarm, accurately report the fault line address, monitor the change of the fault point. Store various fault and operational test signals to display system power status.

3. Reference standard

In recent years, in order to increase the intensity of electrical fire monitoring and prevention, the state has successively formulated or revised a number of relevant standards and regulations to strengthen the prevention of electrical fires. There are:

3.1. GB50045-95 (2005 edition) "Code for Fire Protection Design of High-rise Civil Buildings", which stipulates in Article 9.5.1 that a fire alarm system should be installed in places with high fire risk and dense personnel in high-rise buildings.

3.2. GB50016-2006 "Code for Fire Protection of Building Design", as specified in Article 11.2.7: The following places should be equipped with a residual current action electrical fire monitoring system. These venues include various types of theaters, galleries, warehouses, residential communities, hospitals, shops, schools, and more.

3.3. The relevant provisions of the national standard "Building electrical fire prevention requirements and testing methods" also clearly require that "the residual current action protector that automatically cuts off the power or alarm should be set at the power incoming end".

3.4. The products of the electrical fire monitoring system shall meet: GB14287.1-2005 "Electrical Fire Monitoring Equipment", GB14287.2-2005 "Residual Current Electric Fire Monitoring Detector", GB14287.3-2005 "Measurement Temperature Electric Fire Monitoring and Detection" 》

3.5. The installation and operation of the electrical fire monitoring system shall meet the requirements of GB13955-2005 "Installation and operation of residual current action protection device"

3.6. The power supply of the electrical fire monitoring system shall meet the requirements of GB50052 "Design Specifications for Power Supply and Distribution Systems"

3.7. The design of the electrical fire monitoring system shall meet the requirements of the Design Method of Electrical Fire Monitoring System (Interim Provisions)

4. System composition

The residual current monitoring system of the new construction project of the 10KV squad Shenyang cadre living base substation consists of electrical fire monitoring equipment, electrical fire detectors and leakage current transformers.

The communication bus of this project is connected to two communication buses. After the bus is connected hand in hand in the power distribution room, it is connected to the wall-mounted background to form the aorta of the electrical fire system. The leakage current transformer in the cabinet is connected to the leakage detector through the current line, and the leakage detector displays the leakage condition in real time. The above describes a set of electrical fire monitoring systems with stable signal and reliable accuracy. The system networking is divided into three layers:

1) Station management

The management of the station control management system for the electrical fire monitoring system is the direct window of human-computer interaction and the uppermost part of the system. Mainly composed of system software and necessary hardware equipment, such as touch screen, UPS power supply and so on. The monitoring system software calculates, analyzes, and processes various types of data information on the site, and responds to the on-site transportation situation by means of graphics, digital display, sound, and indicator lights.

Monitoring host: used for data collection, processing, and data forwarding. Provides data interfaces for system management, maintenance, and analysis within and outside the system.

UPS: Ensure the normal power supply of the computer monitoring system, and ensure the normal operation of the station management management equipment when the whole system has power supply problems.

The background monitoring device is set in the self-dimension substation.

2) Network communication layer

Communication medium: The system mainly adopts shielded twisted pair cable, realizes real-time communication between field device and host computer by RS485 interface and MODBUS communication protocol.

3) Field device layer

The field device layer is a data acquisition terminal, mainly for the ARCM200L series of residual electrical fire monitoring detectors.

The system structure topology is as follows:

China Hardware Business Network



5. Electrical fire equipment China Hardware Business Network

5.1, Acrel-6000 electrical fire monitoring background:

The main technical parameters

power supply:

1 rated working voltage AC220V (-15% ~ +10%)

2 Backup power supply: When the main power supply is under voltage or power failure, maintain the monitoring equipment working time ≥ 4 hours

Working system:

24-hour work schedule

communication method:

RS485 bus communication, Modbus-RTU communication protocol, transmission distance 1km, can extend communication transmission distance through repeater

Monitoring capacity:

1 Monitoring equipment can monitor up to 200 monitoring units (detectors)

2 can be connected with ARCM series monitoring detector

Monitoring alarm items:

1 Residual current fault (leakage): fault unit attribute (part, type)

2 Temperature alarm (over temperature): Fault unit attribute (part, type)

3 Current fault (overcurrent): Fault unit attribute (part, type)

Monitoring alarm response time: ≤30s

Monitoring alarm sound pressure level (A weighting): ≥70dB/1m

Monitoring alarm light display: red LED indicator, red light alarm signal should be maintained until manual reset

Monitoring alarm sound signal: can be manually eliminated, can be started again when there is alarm signal input again

Fault alarm item:

1 The communication cable between the monitoring device and the detector is open or shorted.

2 Monitoring equipment main power supply undervoltage or power failure

3 The cable between the charger that charges the battery and the battery is broken or shorted.

Fault alarm response time: ≤100s

Monitoring alarm sound pressure level (A weighting): ≥70dB/1m

Monitoring alarm light display: yellow LED indicator, yellow light alarm signal should be kept until troubleshooting

Fault alarm sound signal: can be manually eliminated, can be started again when there is an alarm signal input again

The normal operation of the non-faulty loop is not affected during the fault

Control output:

Alarm control output: 1 set of normally open passive contacts, capacity: AC250V 3A or DC30V 3A

Self-test items:

1 Indicator check: alarm, fault, operation, main power, standby power indicator

2 display check

3 audio device inspection

Self-test time ≤60s

record:

1 Record content: record type, time of occurrence, detector number, area, fault description, can store no less than 20,000 records

2 record query: query according to the date, type and other conditions of the record

Operational rating:

1 Daily duty class: real-time status monitoring, event record query

2 Monitoring operation level: real-time status monitoring, event record query, detector remote reset, device self-test

3 System management level: real-time status monitoring, event record query, detector remote reset, device self-test, monitoring device system parameter query, monitoring device module detection, operator addition and deletion

Environmental conditions used:

1 Workplace: Fire control room, manned substation (distribution room), wall on room where someone is on duty

2 Working environment temperature: 0 ° C ~ 40 ° C

3 Working environment relative humidity: 5% ~ 95% RH

4 Altitude: ≤2500m

5.2, ARCM200L series instruments

The ARCM200L residual current type electrical fire monitoring detector is designed for TT and TN systems below 0.4kV. It monitors and manages fire risk parameters such as residual current, wire temperature, over current and over voltage in the distribution circuit. Thereby preventing the occurrence of electrical fires and real-time monitoring of various power parameters, providing accurate data for energy management. The product adopts advanced microcontroller technology, with high integration, small size, convenient installation, intelligent, digital and networked. It is an ideal choice for building electrical fire prevention monitoring and system insulation aging prediction. The product complies with the standard requirements of GB14287.2-2005 "Electrical Fire Monitoring System Part 2: Residual Current Electrical Fire Monitoring Detector".

6 system function

6.1. Monitoring alarm function:

The monitoring equipment can receive the leakage and temperature information of multiple detectors, and emit an audible and visual alarm signal when the alarm occurs. At the same time, the red “alarm” indicator on the device lights up, the display indicates the alarm location and alarm type, and the alarm time is recorded. The sound and light alarm is always maintained. Until the display is reset by pressing the display "Reset" button. The audible alarm signal can also be manually removed using the display "Muffler" button. Hardware Business Network Information Center)http://news.chinawj.com.cn

Graphite electrodes are used mainly in ladle furnaces, electric-arc furnace steelmaking, Yellow phosphorus furnace, 
Industrial silicon furnace or melting copper. They are presently the only products available that have the high levels
 of electrical conductivity and the capability of sustaining the extremely high levels of heat generated in this 
demanding environment. High Quality Needle Coke in HP&Uhp Graphite Electrode, to ensure the application for the
 electrodes are more perfect. Graphite electrodes are also used to refine steel in ladle furnaces .
kneading, forming, baking and pressure impregnation, graphitization 
and then precision machined with professional CNC machining. Our
 electrodes have the characteristics of low resistivity, good electrical 
conductivity, low ash, compact structure, good anti oxidation and 
high mechanical strength, and then they are the best conductive 
material for electric arc furnace and smelting furnace.

Our company is specilized in the feild of Graphite Electrode for 27 years in
 China. We have full experiences in exporting RP Hp Uhp Graphite Electrode
 to Russia, Egypt, Pakistan, Bangladesh, Italy, Oman, Malaysia, etc.. 

Graphite Electrode

Graphite Electrode,Ladle Furnace Graphite Electrodes,Eaf Graphite Electrode,Graphite Electrodes Electric Arc Furnace

Carbographite Industrial PTE.LTD , http://www.carbographite.com